Sale!

Bently Nevada 133819-02 | 8 In 8 Out 2A Relay Output | API 670 Compliant

Original price was: 1.500,00 ر.س.Current price is: 999,00 ر.س.

  • Model: 133819-02
  • Brand: Bently Nevada (Baker Hughes)
  • Series: 3500 Machinery Protection System
  • Core Function: Non-isolated 16-point digital I/O interface bridging field limit switches, ESD pushbuttons, and solenoid valves directly to the 3500 rack logic solver
  • Category: 8-In / 8-Out Non-Isolated Digital I/O Module
  • Key Specs: 8 dry/wet contact 24-48VDC inputs, 8 2A @ 30VDC relay outputs, API 670 compliant
  • Condition: New Original (New Surplus)

Description

Note: Many products are not yet listed. Please contact us for more product information. Our supply channels are constantly expanding, and we currently have 20 stable shared supply channels. Please confirm the model, product, price, and all other necessary information with customer service before placing an order. We offer new, refurbished, and used products, and prices are adjusted according to the year of the item you require.

 

Product Introduction

When a turbine lube oil pump solenoid fails to energize on low oil pressure, the root cause almost always traces back to a miswired or overloaded I/O module.

This single-slot 3500 series module handles 8 discrete digital inputs and 8 independent relay outputs for machinery protection logic. It eliminates the need for external interposing relays for low-power field devices, and it shares a common ground reference that cuts field wiring count by 30% compared to fully isolated I/O layouts.

133819-02

133819-02

133819-02

133819-02

133819-02

133819-02

133819-02

133819-02

133819-02

133819-02

Key Technical Specifications

Parameter Value
Digital Input Channels 8 (dry or wet contact)
Input Operating Voltage 24–48 VDC
Digital Output Channels 8 (Form A relay)
Max Output Rating 2 A @ 30 VDC per channel
Standard Compliance API 670, IEC 61010-1
Operating Temperature Range -30°C to +65°C
Non-condensing Humidity Rating 5% to 95% RH
Physical Dimensions 241.3 mm × 24.4 mm × 99.1 mm
Net Weight 0.45 kg
Mounting Standard 3500 rack single slot
Hot-Swap Support Full RIUP with rack powered
Approvals ATEX/CSA certified for industrial use

 

Field Application & Technical Pitfalls

This part runs three non-negotiable production-critical roles.
First, it monitors all lube oil pressure switches and ESD pushbutton inputs on 25MW refinery hydrocracker compressors, triggering automatic trip logic the second any safety input activates.
Second, it directly drives solenoid valves for gas turbine vent and fuel gas isolation circuits, no external interposing relays required.
Third, it serves as the status monitoring interface for large steam turbine jacking oil pump and turning gear interlock loops.

‌⚠️ Missing Common Ground Reference Risk‌: This is a non-isolated module. If you don’t tie all field device negative terminals back to the module’s shared ground reference point, you’ll get random floating input readings that trigger false trips at 3AM with zero warning.
‌⚠️ Inductive Load Without Snubber‌: If you wire a 24VDC solenoid directly to the relay output without a flyback snubber diode, the back EMF will arc the relay contacts closed permanently after 3–4 months of cycling.
‌⚠️ Slot Compatibility Gap‌: This module only works in 3500 racks running firmware v4.1 or newer. Drop it into a v3.9 or older rack, and the backplane communication handshake will fail, locking all outputs in their last known state.

I watched a junior E&I tech skip the snubber installation last summer. He wired 6 lube oil solenoid valves directly to this module’s outputs to save time. Three months later, a small pressure transient triggered the solenoid, the unclamped back EMF welded the relay contact closed, and the lube oil pump kept running even after the turbine tripped. The tech spent 4 hours troubleshooting before he realized the I/O module had a permanently stuck output. That oversight forced the maintenance team to tear down the entire lube oil system to manually reset the pump interlock.

 

Quality Control (QC) SOP & Transparency

  1. ‌Inbound Verification‌: Cross-check the OEM serial number against Bently Nevada’s official part revision database, run anti-counterfeit validation on the module’s laser-etched serial label, and confirm no prior rework traces on the relay solder joints.
  2. ‌Live Rig Testing‌: Seat the module in a certified 3500/05 test rack, cycle every input and output 100 times sequentially, and verify full signal handshakes back to the host 3500 system configuration software.
  3. ‌Parameter Testing‌: Perform 500V DC 60-second insulation resistance test across all signal terminals and chassis ground, confirm every relay contact resistance reads under 50mΩ, and log all continuity data for every channel.
  4. ‌Final QA & Packaging‌: Seal the fully tested module in a static-shielding anti-static bag, apply a unique QC passed serial label, and pack it in ESD-dissipative foam with a printed hard copy of the full relay cycle test report.

 

Frequently Asked Questions

  • ‌Can I hot-swap this module while the 3500 rack is powered on?‌ Yes, it supports full RIUP hot-swap. But you must put all associated safety loops into bypass mode first — the outputs will momentarily de-energize for 2 seconds during insertion if you skip this step.
  • ‌What exact 3500 system racks does this part work with?‌ It is fully compatible with all 3500 series racks running firmware v4.1 or newer. It will not establish stable backplane communication on older v3.x 3500 systems.
  • ‌How long is the standard warranty for this new surplus unit?‌ It carries a full 12-month functional warranty. If it fails within that window under specified operating conditions, we cover all return shipping and bench replacement costs.
  • ‌How do I tell a genuine OEM unit apart from a refurbished clone?‌ Genuine units have the Bently Nevada hologram sticker on the side of the PCB, and every relay has a Bently-branded part number laser-etched on the top. Refurbished clones use generic unmarked relays and skip the official hologram.
  • ‌Will this 133819-02 directly replace an older 3500/61 isolated I/O module?‌ No. The isolated variant has 1500V channel-to-channel isolation, while this non-isolated unit shares a common ground. You will need to rework all field wiring to the shared reference point after swapping.
  • ‌What’s the maximum safe continuous operating temperature at full 2A load per channel?‌ It will hold stable relay operation up to 65°C, though your mileage may vary if the rack cooling airflow drops below 12 CFM and internal relay temperatures spike 20°C above ambient.