Description
Note: Many products are not yet listed. Please contact us for more product information. Our supply channels are constantly expanding, and we currently have 20 stable shared supply channels. Please confirm the model, product, price, and all other necessary information with customer service before placing an order. We offer new, refurbished, and used products, and prices are adjusted according to the year of the item you require.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Part Number | 3BSE013252R1 |
| Supported Protocol | PROFIBUS DP-V1 |
| Maximum Baud Rate | 12 Mbps |
| ModuleBus Interface | Electrical or optical with TB810/TB811 |
| PROFIBUS Address Range | 1–79, rotary switch setting |
| Max Slaves per PROFIBUS Segment | 32 stations |
| Local I/O Backplane | S800 I/O stations |
| Required Terminator | TB807 Modulebus terminator |
| Operating Temperature | -25°C to +70°C |
| Enclosure Rating | IP20, cabinet mounting only |
| Supported Controller | AC800M, 800xA platform |
Product Introduction
ABB CI830 is a Fieldbus Communication Interface for the ABB 800xA and AC800M control platforms. It acts as a bridge between the controller PROFIBUS DP-V1 network and distributed S800 I/O stations. It collects input data and writes output commands across the ModuleBus to local I/O modules.
It uses a dedicated on-board processor to handle bus traffic, reducing controller load. Some newer S800 I/O types are not supported under default firmware, so cross-check the I/O list before rack assembly.

CI830

CI830

CI830

CI830

CI830
Application Scenarios & Field Experience
Many legacy ABB DCS sites run into silent communication drops when aging CI830 units develop optical port degradation. Partial bus failures can freeze I/O data without triggering critical alarms, which creates risk for continuous control loops. This interface restores stable PROFIBUS DP-V1 and ModuleBus communication for existing S800 I/O clusters.
- Pulp and paper mills – pulp stock flow control, valve position feedback for bleaching lines
- Cement manufacturing – kiln temperature and exhaust gas monitoring with distributed S800 racks
- Hydroelectric power plants – turbine auxiliary I/O and gate position control networks
- Refinery auxiliary systems – cooling water pump status and pressure transmitters on remote I/O racks
In my experience, a pulp mill had intermittent loss of 12 S800 I/O modules on one PROFIBUS segment. The CI830 optical ModuleBus port had developed signal attenuation. The maintenance team locked the control loop, swapped the module, set the correct rotary address, fitted the TB807 terminator, and verified bus scan within 35 minutes. No unplanned trip occurred, and all analog and digital signals returned to normal trending.
Standard Operating Procedure (SOP) for Quality Control
- Visual & Origin Inspection: Verify OEM packaging, factory labels, and part marking; cross-check serial number against counterfeit reference records.
- Live Rig Testing: Mount on a test AC800M rack, connect PROFIBUS bus, confirm all slave stations scan in.
- Firmware Verification: Record installed firmware revision; flag revisions that block newer I/O types.
- Protocol Handshake Check: Validate both electrical and optical ModuleBus communication paths where applicable.
- ESD-Safe Packaging: Place tested module in anti-static bag, add foam cushioning, and seal in labeled outer carton for transit.
Frequently Asked Questions
Q1: Can I replace CI830 directly with CI801 on an existing rack? A: No. CI801 uses different hardware and firmware mapping. It is a newer replacement part for new builds, not a drop-in swap for CI830. Verify exact load capacity with the OEM datasheet.
Q2: What warranty comes with this ABB CI830? A: We provide a 12-month warranty. The warranty covers factory defects, but it does not cover damage from bus surges, miswiring, or incorrect terminator installation.
Q3: How quickly can this unit ship if marked in stock? A: Stock units ship within 1–2 business days after payment confirmation. Lead time for units not in stock depends on the procurement portal supply chain.
Q4: What happens if the firmware revision does not match the existing modules? A: Mismatched firmware can cause missing I/O points, slave scan failures, or intermittent bus timeouts. Confirm the firmware compatibility matrix before installation.
Q5: Can I hot-swap while the PROFIBUS segment is active? A: Do not hot-swap this module unless the bus is configured with redundant communication pairs. Non-redundant hot-swap will drop all I/O on that segment and trigger process alarms.