Description
Note: Many products are not yet listed. Please contact us for more product information. Our supply channels are constantly expanding, and we currently have 20 stable shared supply channels. Please confirm the model, product, price, and all other necessary information with customer service before placing an order. We offer new, refurbished, and used products, and prices are adjusted according to the year of the item you require.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Total Output Channels | 40 fully triplicated TMR analog output channels |
| Channel Grouping | 5 isolated banks of 8 channels each |
| Output Signal Ranges | 0–20 mA, 4–20 mA |
| Resolution | 12-bit |
| Calibration Accuracy | ±0.1% full scale at 25°C; ±0.25% across full temperature range |
| Step Response | <50 ms to settle within 1% of final value |
| Galvanic Isolation | 2500 V impulse withstand |
| SOE Time Stamp Resolution | 1 ms |
| Operating Temperature | 0 °C to +60 °C |
| Power Supply | 20–32 VDC backplane feed |
| Safety Certification | IEC 61508 SIL 3, TÜV, UL/cUL, CE |
| Matching FTA | T8850 field termination assembly |
| Enclosure Rating | IP20, cabinet mounting only |
Product Introduction
The ICS Triplex T8480 is a high-density TMR analog output module built for the Trusted 8000 safety platform. It receives validated setpoint data from the safety controller and outputs analog current signals to control valves and positioners.
Each channel uses 2oo3 voting logic. A single fault on one signal leg does not force a faulty output. Built-in loop diagnostics detect open circuits and short circuits before the control loop drifts outside safe bounds.

T8480

T8480

T8480

T8480

T8480
Application Scenarios & Field Experience
Many safety control loops suffer from unpredictable valve drift when a single output circuit fails. Standard non-TMR analog output cards can drive a valve to an unsafe position without prior warning. The T8480’s triple voting structure rejects faulty leg signals while maintaining a stable 4–20mA output.
- Offshore oil and gas facility: ESD-regulated control valve positioning for fuel gas and choke valves.
- Refinery hydrocracker unit: Analog output for pressure control valves under SIS supervision.
- Combined-cycle power plant: Boiler feedwater valve modulation within safety interlock limits.
- Batch chemical plant: Solenoid and control valve positioning for hazardous reagent feed loops.
In my experience, a petrochemical plant found a corrosion-induced short on one leg of a T8480 channel during routine diagnostics. The remaining two voted paths held the valve setpoint steady. The team scheduled replacement during the next unit shutdown. No unsafe valve movement or process excursion occurred.
Standard Operating Procedure (SOP) for Quality Control
- Visual & Origin Inspection: Check OEM packaging, printed board markings, serial numbers, and anti-counterfeit markers against OEM documentation.
- Live Rig Testing: Install module on compatible Trusted chassis, apply 24 VDC supply, run power-on self-test, confirm backplane communication and LED status.
- Firmware Verification: Read and record firmware revision; match revision against the order bill of materials.
- Loop Simulation Test: Pair with T8850 FTA, drive 4–20mA spans and verify voting, open-loop and short-circuit fault flags.
- ESD-Safe Packaging: Seal in static-dissipative bag, add foam cushion, rigid outer carton, and ESD warning labels before shipment.
Frequently Asked Questions
Q1: Is the T8480 compatible with older Trusted 8000 chassis and processor modules? A: It fits standard T8100 and T8300 chassis. Always verify processor firmware revision; older firmware builds may not support newer T8480 variants. Review the OEM compatibility matrix before swap.
Q2: What warranty coverage do you provide for this T8480 module? A: We offer 12 months warranty. Warranty covers factory-tested hardware defects; it does not cover surge damage, miswiring, or improper hot-swap execution.
Q3: Can this item ship immediately, or do we need to confirm stock lead time? A: Stock status updates on our website. If marked in stock, shipment can start within 1–3 business days. If inventory is depleted, we will quote confirmed lead time before order lock.
Q4: What happens if firmware revision does not match the existing safety system? A: Mismatched firmware can trigger backplane handshake faults or disable loop diagnostics. Do not install the module live without a pre-install firmware review. We can supply the revision you specify if available.
Q5: Can I hot-swap the while the safety system is running? A: Hot-swap is supported on the Trusted platform, but you must bypass the affected control loop first. Do not hot-swap active regulated safety loops without bypass approval, or you risk unwanted valve movement and a process trip.
今天 10:09
What are the key features of the ICS Triplex ?
Can the ICS Triplex be used in harsh industrial environments?
Where can I purchase the ICS Triplex ?