Sale!

GE Multilin SR489-P1-LO-A20-E | Genuine OEM Generator Relay

Original price was: 5.500,00 ر.س.Current price is: 4.000,00 ر.س.

  • Model: SR489-P1-LO-A20-E
  • Brand: GE Multilin (GE Grid Solutions)
  • Series: 489 Generator Management Relay
  • Core Function: Protects a generator with differential, overcurrent, voltage/frequency, and trip logic while feeding metering and status to the plant network.
  • Category: Generator protection and management relay
  • Key Specs: Order-code variant with CT/VT inputs and communications set by suffix; drawout case; EnerVista configuration
  • Condition: New Original (New Surplus) / Refurbished

Description

Note: Many products are not yet listed. Please contact us for more product information. Our supply channels are constantly expanding, and we currently have 20 stable shared supply channels. Please confirm the model, product, price, and all other necessary information with customer service before placing an order. We offer new, refurbished, and used products, and prices are adjusted according to the year of the item you require.

 

3. Product Introduction

When a generator trips on a differential alarm and the outage clock starts, the relay is often the part nobody wants to guess about. The GE Multilin SR489-P1-LO-A20-E is a 489 Generator Management Relay built for generator protection and control in one drawout case. It takes CT and VT inputs, runs protection and metering functions, and trips the breaker through binary outputs. The order-code string decides fitted communications and input options, so match every character against the old label before you order (—though your mileage may vary depending on firmware and panel wiring).

SR489-P1-LO-A20-E

SR489-P1-LO-A20-E

SR489-P1-LO-A20-E

SR489-P1-LO-A20-E

SR489-P1-LO-A20-E

SR489-P1-LO-A20-E

SR489-P1-LO-A20-E

SR489-P1-LO-A20-E

SR489-P1-LO-A20-E

SR489-P1-LO-A20-E

4. Key Technical Specifications

Parameter Value
Order Code SR489-P1-LO-A20-E
Product Type Generator protection and management relay
Series 489 Generator Management Relay
Protection Functions Differential, overcurrent, voltage/frequency, reverse power, loss of excitation — confirm licensed set
CT Inputs Rated current set by order code; verify 1 A/5 A configuration with OEM datasheet
VT Inputs Verify channel count and rated voltage with OEM datasheet
Binary I/O Count and type set by order code — confirm against OEM table
Communications Ethernet and serial options per order code; verify fitted protocols
Auxiliary Supply Verify A20 code against OEM datasheet
Mounting Drawout case with test facilities — verify panel cutout
Configuration Tool EnerVista 489 setup software; settings file must match firmware
Operating Temperature Verify exact range with OEM datasheet

 

5. Field Application & Technical Pitfalls (The Engineer’s Guide)

Where this relay is critical:

  • Industrial captive power plants where a generator feeds plant loads and a protection misoperation drops production.
  • Combined heat and power generators paralleled with the utility where reverse power and loss-of-excitation elements must coordinate with the utility interface.
  • Standby and black-start generators where protection settings must hold through low-fault-current conditions during islanded operation.

Three pitfalls that bite during replacement:

  • Order code and fitted-option mismatch. Warning: “SR489” alone tells you almost nothing. Two relays with the same family name can differ in CT rating, communications, and binary I/O. A unit that powers up and shows metering can still lack the Ethernet port or input rating your panel expects. Compare every character against the old label and the OEM order-code table.
  • CT/VT polarity, ratio, and differential pairing. Warning: never work on CT circuits with the primary energized — an open CT secondary develops dangerous voltage. Use the test switch to isolate trip outputs, verify CT polarity and ratio against the drawing, and confirm the differential CT pair matches the relay’s expected configuration. A reversed CT pair turns a forward fault into a reverse decision and defeats the differential element.
  • Settings file, firmware, and trip-circuit isolation. Warning: load the site’s EnerVista settings file and verify the relay’s protection functions are licensed before energizing trip circuits. A replacement with newer firmware can reject the old file or silently change a function’s behavior. Confirm the relay’s communication address and technical key, because the plant network will not accept a duplicate or mismatched identity.

Lesson learned: A crew replaced a failed 489 with a spare that carried the right family name but a different order-code suffix. The relay energized, metering looked normal, and the generator ran for two days — until a differential event failed to trip. Root cause: the replacement’s CT input rating and differential configuration did not match the panel. The relay was good; the order code was not.

 

6. Quality Control (QC) SOP & Transparency

  1. Inbound Verification. Each relay is checked against the OEM packing list, label typography, full order code, serial number format, and date-code range. The order-code suffix is decoded and logged before the unit enters stock.
  2. Live Rig Testing. The relay is powered on the bench at rated auxiliary supply, connected to EnerVista, and checked for relay identity, firmware revision, and installed function set. Binary inputs and outputs are exercised where the test fixture supports them.
  3. Parameter Testing. Auxiliary supply current draw, binary output continuity, CT/VT input circuit checks, and communication port status are verified per the OEM commissioning guidance where published. Undocumented values are flagged for buyer confirmation rather than guessed.
  4. Final QA & Packaging. The relay ships in protective packaging with a QC-passed label, a test record showing the firmware revision and decoded order code we verified, and photos of the terminal and communication module layout when available.

 

7. Frequently Asked Questions (FAQ)

Can I swap this relay with the generator running? No. Isolate the trip circuits and auxiliary supply first, and use the test switch to block tripping. Then confirm CT circuits are shorted or isolated before you touch the terminals.

How do I confirm the order code matches my existing relay? Send the label photo from the old unit plus your EnerVista settings file name. We decode the suffix characters and cross-check the test record before shipping. Exact fit depends on the whole string, not just the 489 family name.

What’s the warranty? 12 months from delivery for functional failure under normal operation. Communication modules and other accessories, if supplied separately, carry a 90-day replacement guarantee.

How can I tell genuine OEM from refurbished? Genuine units carry the original GE Multilin label with consistent typography and a traceable serial number. Refurbished units carry our QC tag in addition to the OEM label, and we disclose condition on the quote.

Does it ship with a settings file or license? No. We ship a test record, not your protection settings. Load your EnerVista project and confirm the licensed function set before the relay goes into service.

Can you test the protection functions before shipment? We verify identity, firmware, I/O, and communication on the bench. Full secondary injection against your settings is a commissioning activity, and we will tell you exactly what we did and did not test.

zyq xuanchuance