Description
Note: Many products are not yet listed. Please contact us for more product information. Our supply channels are constantly expanding, and we currently have 20 stable shared supply channels. Please confirm the model, product, price, and all other necessary information with customer service before placing an order. We offer new, refurbished, and used products, and prices are adjusted according to the year of the item you require.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Product Type | PLC Processor Module |
| Manufacturer | Schneider Electric |
| Product Family | Modicon Quantum |
| Model | 140CPU43412A |
| Processor | Intel 80486 |
| Clock Frequency | 66 MHz |
| Internal RAM | 896 KB |
| Mathematical Coprocessor | Included |
| Logic Execution Time | 0.1–0.5 ms per 1K LL984 instructions |
| Watchdog Timer | 250 ms, software adjustable |
| Serial Communication | 2 × Modbus RS-232 |
| Network Communication | 1 × Modbus Plus (RS-485) |
| Maximum Option Modules | 6 NOM, NOE, CR, or NMS modules |
| Bus Current Requirement | 1.25 A |
| Battery Capacity | 1.2 Ah |
| Operating Temperature | 0–60°C |
| Storage Temperature | -40–85°C |
| Relative Humidity | Up to 95%, non-condensing |
| Programming Software | Concept, ProWORX 32, Modsoft |
The 140CPU43412A is an earlier-generation Quantum processor. Schneider Electric lists it as discontinued, with end of service reached in September 2025 on its UK product record. It is therefore primarily relevant to existing-system maintenance and replacement requirements.
Product Introduction
The Schneider Electric 140CPU43412A is a central processing unit for the Modicon Quantum PLC platform. Built around an Intel 80486 processor running at 66 MHz, it provides 896 KB of internal RAM and supports PLC applications developed with Concept and ProWORX 32. Its communication interfaces include two Modbus RS-232 ports and one Modbus Plus network port.
This CPU is designed for established Quantum control systems that require continued operation and maintenance. The “A” suffix is important: this version uses a distinct flash executive from the non-A model. When replacing an existing processor, verify the executive version, programming environment, and Hot Standby arrangement rather than relying on the base model number alone.

140CPU43412A

140CPU43412A

140CPU43412A

140CPU43412A
Application Scenarios & Field Experience
In a legacy Quantum PLC installation, the CPU manages the control program, I/O data exchange, and communication with other system components. A processor failure can affect the entire control station, making replacement a high-priority maintenance task. However, CPU replacement is not simply a matter of inserting another module. The processor suffix, flash executive, application backup, battery condition, communication settings, and rack configuration all need to be checked.
Typical application scenarios
- Water and Wastewater Treatment — Executes control logic for pumping stations, treatment processes, and distributed I/O connected to a Quantum PLC system.
- Power Generation — Maintains PLC control of auxiliary systems, equipment interlocks, and plant monitoring functions.
- Oil and Gas Processing — Supports legacy process control applications that exchange data through Modbus and Modbus Plus networks.
- Industrial Manufacturing — Runs established machine and production-line control programs where the original Quantum architecture remains in service.
Illustrative engineering scenario, not a documented customer installation: A manufacturing plant experiences a CPU fault in an operating Quantum rack. Before replacement, the maintenance team retrieves the application backup and records the original processor’s full part number, executive version, key-switch position, and communication settings. The replacement 140CPU43412A is checked against the existing configuration, with particular attention to the A-version flash executive. The team then verifies program execution, I/O communication, and Modbus network connections before returning the equipment to service.
Standard Operating Procedure (SOP) for Quality Control
1. Visual & Origin Inspection
- Verify the Schneider Electric label, full part number, and serial number.
- Inspect the module housing, backplane connector, communication ports, key switch, and battery compartment.
- Check for corrosion, damaged pins, cracked components, or signs of unauthorized repair.
- Review available OEM packaging and origin documentation.
2. Functional Testing
- Where a compatible Modicon Quantum rack is available, verify CPU startup and module recognition.
- Check the diagnostic indicators and processor status.
- Verify the two Modbus RS-232 ports and Modbus Plus communication interface using suitable test equipment.
- Where a test application is available, check program execution and I/O data exchange.
- Record the test setup, results, and any functions that could not be tested.
3. Firmware & Configuration Verification
- Record the installed flash executive version.
- Confirm compatibility with the existing Concept or ProWORX 32 project.
- Check the application backup, key-switch position, communication settings, and memory status.
- For Hot Standby systems, confirm that both processors use the same A-version or non-A-version configuration. The A and non-A flash executives are not interchangeable.
- Verify battery condition and data-retention requirements before commissioning.
4. ESD-Safe Packaging
- Handle the CPU using appropriate electrostatic-discharge precautions.
- Protect the backplane connector and communication ports.
- Use anti-static packaging and suitable cushioning to prevent impact damage.
5. Pre-Shipment Documentation
- Provide actual product photos and clear label photos.
- Confirm the complete model number and visible hardware details.
- Provide available inspection records and test results for checks actually completed on the specific unit.
Frequently Asked Questions (FAQ)
Q1: Can the 140CPU43412A replace the 140CPU43412 directly?
A: The two models are functionally similar, but their flash executives are different and not interchangeable. For Hot Standby applications, both CPUs must be the same version: either two A models or two non-A models. Verify the installed executive and system configuration before replacement.
10/2019+1
Q2: What warranty do you provide for the 140CPU43412A?
A: We offer a 12-month warranty, subject to confirmed order terms. Product condition and warranty coverage will be stated in the order confirmation.
Q3: Is the 140CPU43412A available for immediate shipment?
A: Stock availability and condition must be confirmed before ordering. For confirmed available stock, our usual arrangement is shipment within one week after payment. Product photos and live video inspection can be arranged before shipment.
Q4: Does the CPU firmware or executive version affect compatibility?
A: Yes. The A version has its own flash executive, which cannot be interchanged with the non-A version. The processor is intended for Concept, ProWORX 32, and Modsoft environments. Check the installed executive and project requirements before loading or transferring an application.
10/2019+1
Q5: What should engineers check before installing a replacement CPU?
A: Back up the application and record the existing executive version, key-switch position, battery status, and communication settings. Confirm the Hot Standby configuration, if applicable, and verify the rack’s power capacity. Follow the approved shutdown and commissioning procedure; do not assume that the replacement can be inserted or exchanged while the system is energized.
Lifecycle note: Schneider Electric has discontinued this processor and lists the M580 BMEP582040 as a recommended replacement. This is a platform migration option, not a direct plug-in substitute for the Quantum CPU.